Answers to questions frequently asked by service technicians |
|
|
| |
| I
have a job on which it is difficult to clean up the fire. What should I
do? |
- Check
the fire to see whether it is off center (see discussion
of off-center fires in next question).
- Check
the fan blades and if they are covered with lint and dirt, clean them.
- If
this is a conventional oil burner, check for a burned-off-end cone.
- Check
the oil pressure to be sure that it is at least 100 psi.
- Check
for a plugged line filter or pump strainer.
- If
the smoke is at the outside edges of the fire, it might be well to try
a wider spray angle.
- If
the smoke occurs at the end of the fire, it might be well to try a wider
spray angle.
- The
burner may have insufficient air capacity for the firing rate.
- The
burner may have too high air capacity for this firing rate. This would
mean that the burner head couldn't handle a low firing rate.
- It
might just be a very inefficient burner, which cannot be made to burn
clean.
- The
nozzle may be partially plugged, resulting i poor atomization.
- The
oil may have a high viscosity or it might be cold, resulting in collapsing
spray.
- Get
sufficient air into the boiler room. If necessary, put in an air intake
pipe with a screen and storm cover.
|
|
| The
fire in a burner is always off center and heavy on the right side. I can't
find a nozzle that will straighten up the fire. |
- If
the flame is always heavy on one side, the nozzle does not cause it.
It would be impossible to make a nozzle spray that is heavy on one side
and always have it come up on the same side of the burner.
- Check
the position of the nozzle in the burner head. The chances are it is
off to one side or the other.
- With
a short burner tube, the air stream may be stronger on one side than
the other. That will give the appearance of being heavy one side.
- If
the nozzle spray pattern is off center due to contamination or any other
reason, it may mike a flame, which is heavy on one side, but it could
be in any direction.
|
|
| How
do you cure pulsation? |
- A
hollow cone nozzle generally gives greater freedom from pulsation than
a solid cone nozzle.
- A
wider spray angle sometimes helps a pulsation condition. It may even
be necessary to use a 90 degree nozzle. In this case watch for smoke
at the outer edges of the fire.
- Reduce
the firing rate to the next smaller nozzle if it will carry the heating
load.
- The
combustion chamber may be too large, allowing the fire to leave the
burner.
- Higher
oil pressure sometimes helps because it gives a more stable spray pattern
and smaller droplets, which burn closer to the burner.
- Be
sure there is air intake into the boiler room.
- Sometimes
a flame retention burner will cure or improve a pulsating or rumbling
condition.
|
|
| I
have a customer who complains of having soot particles on the floor around
the boiler and other places in the basement. The fire is clean. What is
the reason for this? |
- Make
sure that you have adequate chimney draft so that there is not a back-pressure
in the smoke pipe when the burner starts. This type of complaint occurs
with a long smoke pipe between the boiler and the chimney. If the smoke
pipe does not have enough pitch, there may be a back-pressure at the
boiler connection even with sufficient chimney draft.
- Check
for an obstruction at the point where the smoke pipe enters the chimney.
- Cement
up all leaks in the boiler setting where soot might come out on the
start.
- Install
a delayed opening solenoid valve or ProTek valve in the nozzle line
to make smoother starts.
|
|
|
If the burner sometimes fails to ignite
smoothly and starts with a puff, what can be done to improve it? |
- Check
the electrode points for proper spacing. The points should be 1/8"
to 3/16" apart, 9/16" above the centerline of the nozzle and
then spaced correctly forward from the face of the nozzle for each different
spray angle.
- Clean
carbon and dirt from the points and from the insulators.
- The
transformer may be weak and not delivering full voltage or current.
If you don't have another transformer immediately available, file the
electrodes to a sharp point. This will give a better spark.
- Check
for cracked insulators. Sometimes an insulator may be cracked under
the electrode bracket and it is difficult to find. This could cause
a high voltage leak, thus reducing the voltage at the points.
- A
partially plugged nozzle causing off-center spray can cause delayed
ignition.
- Above
about 2.50 gph a hollow cone spray sometimes may cause delayed ignition.
Changing to a solid cone sometimes helps that situation.
- The
air setting on the burner may be wide open, thus tending to blow the
fire out before it is established. Adjust the air correctly.
|
|
| I
have tried firing fractional gallonage nozzles and they only work two or
three weeks and plug up. Does everyone have that same problem? |
- Fractional
gallonage nozzles have become a very popular nozzle and are giving good
satisfaction if properly used. First of all, do not remove a nozzle
from it vial before you are ready to install it in the burner. That
may contaminate it.
- Be
sure an adequate supply line filter is installed. This size nozzle should
have a filter capable of removing particles over 50 microns. The problem
is to know which filter will do that. Generally speaking, the paper
filters are finer than the felt or woven filters that are generally
available.
- Install
a Delavan line filter for extra nozzle protection. Make sure all trapped
air is removed and follow installation instructions.
- The
Delavan Del-O-Flo nozzle may help. It was designed especially to minimize
the usual plugging problems associated with low flow rates.
- Flush
or blow out the nozzle line and adapter before installing the nozzle.
- If
the nozzle runs exceptionally hot, find out why and remove the cause.
|
|
|
 |
|